S4.2 – I thought the building was c1919? I agree this needs to change to 1919 and 1940 is incorrect. S4.3 – what access controls could you use to the wheelchair access – keypad type? Generally, if it is only visitors, then a call point would be sufficient. However if you expect any disabled user will be gaining access when the building is empty, then you will have to provide a key pad access. S4.4 – all existing internal doors are being retained with only a few new doors being added, only new ironmongery has been specified. I guess we just have to update to say the same and explaining that where we are changing it will meet Part M regulations. One other issue picked up on site is that PDX.02 opens inwards and not outwards as shown on